temperature-data-logger-specifciation

temperature-data-logger-specifciation

Wireless Ethernet Temperature Data Logger
>> Measure and Record 2 Temperature Readings Using External Sensors
>> -40°C to 110°C Temperature Recording Range with ±0.3°C Temperature Accuracy
>> Configure, Setup and Manage Data Loggers over an Internet Connection and Browser
>> T&D WebStorage Service, WebViewer and Current Readings Monitor Software Included
>> Stores up to 8,000 Sets of Recorded Readings onto Internal Non-Volatile Memory
>> User-Configurable Sampling Rate: 1 Second to 1 Hour
>> Email Alarm Notifications and Optional External Contact Terminal for Electromagnetic Contactor
>> AC Powered with Battery Backup for Power Failures and Emergency Use Only
>> Automatic Sending of Measured Readings via FTP or E-mail
Ethernet Temperature Data Logger Specifications
Measurement Temperature Using (2) External Thermistor Sensor (#TR-0106)
Temperature Range: -40°C to 110°C
Accuracy: ±0.3°C (-20°C to 80°C); ±0.5°C (Other)
Resolution: 0.1°C
Response Time: About 190 Seconds to 90%
Thermal Time Constant: About 75 Seconds
Data Storage Capacity 8,000 Samples/Readings
Alarms High and Low Threshold Alarm Conditions with Email, Notification and External COntact Output Terminal for Buzzer, Siren, Lamp, or Electromagnetic Contactor
External Output Terminal Alarm Output Terminal
Voltage When OFF: AC/DC less than 50 Volts
Voltage When ON: Less than 0.1 Amp
Resistance When ON: About 35Ω
Sampling Interval 1,2,5,10,15,20,30 Seconds / 1,2,5,10,15,20,30,60 minutes
(Total of 15 Choices)
Recording Mode Endless: Overwrite Oldest Data when Capacity is Full
LCD Display Items Current Readings / Recording Settings / Battery Life Warning / Over Measurement Range Warning / Amount of Recorded Data
Power AC Adaptor (#AD-0638 – Included)
Battery Backup: CR-2032 Lithium Coin Cell (Included)
NOTE: Battery is for Data Backup During Power Failure and Emergency USe Only. No Network Communications Available During Battery Operation.
Data Backup Approx. 3 Months on Battery Only
Communication Protocols HTTP, SMTP, FTP, SNTP, DHCP and DNS
NOTE: SMTP Options: POP before SMTP, SMTP-AUTH
Communication Types Wireless LAN: Wireless Antenna IEEE 802.11b/g WEP/WPA-TKIP/WPA-2-AES
USB: Cable Attached from Computer to Data Logger – For Setup Only
OS Compatibility Windows 8 and 7 (32-bit and 64-Bit Versions), Vista and XP (32-Bit)
NOTE: For Windows 8, Software Should Be Used in “Desktop” Mode Only
Supported Browsers Desktop: IE 6.0+, Firefox 15.0+, Chrome 22.0+, Safari 6.0+
Mobile: Safari (iOS); Chrome (iOS, Android), Firefox (Android)
Operating Environment Temperature: -10°C to 60°C
Humidity: 90% RH or Less (No Condensation)
Monitoring Functions WebViewer: View Data Graphs, Current Readings and Settings in Browser
T&D WebStorage Service: “Anytime, Anywhere” Complete Management of Recorded Data and Data Logger
Current Readings Monitor: Management of Current Readings of all Registered Devices on Same Network
Mobile Devices: WebViewer Software and T&D WebStorage Service compatible with Smart Phones and Tablets
Standards Compliance CE, FCC
Dimension 55mm x 78mm x 37mm
(Excluding Protrusions)
Weight 80 grams
(Including Battery, Excluding Sensor)